Permit Number: T09CM02105
Parcel: 140230410

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM02105
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Need structural evaluation for HVAC unit trade out on roof
08/06/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Project
T09CM02105
5845 S. Southland Bl

1. Provide 30 amp overcurrent protection for AC unit in panel
2. Indicate 10 awg conductors to be used for AC unit
3. Provide Disconnecting Means for AC unit witrin sight
4. Provide roof top service GFI receptacle within 25 feet

Rich Jiroudek
Electric Plan CK
8/6/09
08/06/2009 JASON GREEN ENGINEERING REVIEW Passed
08/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the SEER for the proposed split system A/C unit.
2. Verify that the existing duct insulation has a vapor barrier.
3. Explain how the condensate will be handled.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2009 CINDY AGUILAR OUT TO CUSTOMER Completed