Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM02105
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Need structural evaluation for HVAC unit trade out on roof |
| 08/06/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project T09CM02105 5845 S. Southland Bl 1. Provide 30 amp overcurrent protection for AC unit in panel 2. Indicate 10 awg conductors to be used for AC unit 3. Provide Disconnecting Means for AC unit witrin sight 4. Provide roof top service GFI receptacle within 25 feet Rich Jiroudek Electric Plan CK 8/6/09 |
| 08/06/2009 | JASON GREEN | ENGINEERING | REVIEW | Passed | |
| 08/06/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the SEER for the proposed split system A/C unit. 2. Verify that the existing duct insulation has a vapor barrier. 3. Explain how the condensate will be handled. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/13/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |