Permit Number: T09CM02104
Parcel: 13316030E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02104
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2009 TERRY STEVENS ZONING REVIEW Approved
08/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/06/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Project
T09CM02104
6375 E. Tanque Verde RD

1. Panel P1C shows main breaker on panel of 175 amps with load of 196amps on panel after renovation.
-please verify existing feeder size and main breker size

Rich Jiroudek
Electric Plan CK
8/06/09
520-837-4988
08/06/2009 ROBERT SHERRY WATER REVIEW Approved
08/06/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/06/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
08/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/06/2009 JASON GREEN ENGINEERING REVIEW Approved
08/06/2009 DAVE MANN FIRE REVIEW Approved
08/06/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
08/06/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/06/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY