Permit Number: T09CM02103
Parcel: 140230420

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM02103
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2009 JASON GREEN ENGINEERING REVIEW Passed
08/06/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Project
T09CM02103/5843 S. Southland Bl

1. see comments from T09CM02105

Rich Jiroudek
Electric Plan CK
8/6/09
08/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the SEER for the proposed split system A/C unit.
2. Verify that the existing duct insulation has a vapor barrier.
3. Explain how the condensate will be handled.
08/13/2009 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2009 CINDY AGUILAR OUT TO CUSTOMER Completed