Permit Number: T09CM02095
Parcel: 140420200

Address:
2801 E ELVIRA RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM02095
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Drawing M1.0 appears to have been plotted with some ductwork layers turned off; replot for clarity. Reference: Section 106.3.1, IMC 2006.
2. Provide a smoke detector in the return air duct for HP-2, upstream of any outside air connections. Reference: Section 606.1, IMC 2006.
11/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM02095
2801 E. Elvira RD.

1.
11/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied The electrical plans have been denied for the following;

1. Provide the fault current for the Transfer Switch
2. The new transfer switch notes a S.N.( Soild Neutral) ? If this is the case, the grounding electrode conductor would not need to tie into the neutral at the generator, what would the case be?
3. Indicate ground sizes to be used in new conduits.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2009 THAUSER1 OUT TO CUSTOMER Completed
12/01/2009 SUE REEVES REJECT SHELF Completed