Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM02095
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Drawing M1.0 appears to have been plotted with some ductwork layers turned off; replot for clarity. Reference: Section 106.3.1, IMC 2006. 2. Provide a smoke detector in the return air duct for HP-2, upstream of any outside air connections. Reference: Section 606.1, IMC 2006. |
| 11/05/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM02095 2801 E. Elvira RD. 1. |
| 11/05/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | The electrical plans have been denied for the following; 1. Provide the fault current for the Transfer Switch 2. The new transfer switch notes a S.N.( Soild Neutral) ? If this is the case, the grounding electrode conductor would not need to tie into the neutral at the generator, what would the case be? 3. Indicate ground sizes to be used in new conduits. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/01/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 12/01/2009 | SUE REEVES | REJECT SHELF | Completed |