Permit Number: T09CM02091
Parcel: 123081330

Address:
2737 E HELEN ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02091
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2009 RONALD BROWN BUILDING-RESIDENTIAL REVIEW Denied GENERAL
1. Throughout all of the sheets of the documnets, font sizes are less than 3/32". Please revise all lettering to a minimum of 3/32", lower and upper case.
SITE PLAN
2. Please show location of all utility lines and meters from property line to building, R106.1.1.
FLOOR PLANS
3. Please label all rooms and spaces. What is the space in the middle of the new addition, first floor.
4. Please identify ceiling heights in all areas. Note average height at sloped ceiling areas, R305.1.
5. Letter size of all doors and windows is way too small, can't read the notes. Provide all window types, and designate the operable portion of windows.
STAIR
6. Pleasep rovide details and dimensions for stairways. (36" width min, 10" min. tread depth, 7 ¾" max.
riser height, R311, R312.
FOUNDATION AND STRUCTURAL FRAMING PLANS
7. Please submit Special Inspectors form for approval.
8. Structural notes indicate IBC as the governing code. The project is residential and as per the front cover should be complying with the 2006 IRC.
9. Please specify lumber grade/species, or manufacturer and series for glue-lams and "I" joists, R802.1.
ELEVATIONS
10. Please specify height above grade for finished floor, windows/doors, exterior walls, rooflines, porches,
chimneys, etc.
SECTIONS - DETAILS
11. Please cross-reference all cross-sections to the floor plan and framing plans.
12. Stucco: Show weep screeds with a min. clearance 4" above grade or 2" above paved areas, R703.6.2.1.
ENERGY CONSERVATION CODE
13. Please provide a note requiring the insulation certificate shall be posted in the electrical distribution panel.

END OF REVIEW

before final inspection, N1101.8.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2009 CPIERCE1 OUT TO CUSTOMER Completed