Permit Number: T09CM02073
Parcel: 125070090

Address:
2549 E 3RD ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02073
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2009 GERRY KOZIOL WWM REVIEW Approved
10/14/2009 RONALD BROWN BUILDING-RESIDENTIAL REVIEW Denied GENERAL
1. Need code reference to 2006 IRC
2. Need to provide a minimum 3/32" font sizes on sheet A3, Electrical Load Calculations.
SITE PLAN
3. Need to show location of all utility lines and meters from property line to building, R106.1.1.
FLOOR PLAN
4. Identify ceiling heights in all areas. Note average height at sloped ceiling areas, R305.1.
5. Show the location of attic access min. 22"x30", R807.
6. No door/window schedules provided. Show size of all doors and windows. Provide all window types, and designate the operable portion of windows.
FOUNDATION
7. Provide a note for termite treatment, R320 as amended.
ELEVATIONS
8. For thin-coat stucco systems, indicate the ICBO #, system name, and vapor barrier, R703.6.
SECTIONS/DETAILS
9. Specify wall and ceiling covering. Note: Ceiling gypsum board must be either 5/8" or ½" sag resistant
when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
ELECTRICAL PLANS
10. Check dishwasher electrical requirements. Most only need 120v.
11. Show location of existing electrical panel.
12. Electrical work shall comply with 2006 IRC chapters 33 - 42 not the 2005 NEC.
PLUMBING PLANS
13. Show waste line connection and VTR for relocated dishwasher on plumbing plan.
14. Provide vent sizes, UPC 904. Provide vent piping through the roof so that the aggregate cross-sectional area shall not be less than that of the largest required building sewer, UPC 904.1.
15. Show trap arms within acceptable distances from plumbing vents, UPC Table 10-1.
MECHANICAL PLANS
16. Two exhaust inlets are not required for the toilet. One will suffice especially with a 250 CFM exhaust fan.
17. Show supply and return ducts with minimum R-8 insulation, R1103.2.1. not R-6 as per note "C".
18. Show the condensate line and secondary for HVAC unit, M1411.3
ENERGEY CONSERVATION CODE
19. Provide a note requiring the insulation certificate shall be posted in the electrical distribution panel
before final inspection.

END OF REVIEW