Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02072
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2009 GERRY KOZIOL WWM REVIEW Approved
08/28/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM02072

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007; the 2006 UPC with amendments on 7/10/2007; effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1.

FOUNDATION PLANS:

1. Show compliance with termite treatment, R320 as amended.

FLOOR PLANS:

1. Show a floor plan labeling all proposed and adjacent rooms and spaces, R106.1.1. Bedrooms have additional requirements from other living spaces.

STRUCTURAL PLANS:

1. Note the size and spacing of ledger anchorage to block or framed wall, R301.1.

SECTIONS - DETAILS:

1. Show wood framing resting on concrete as pressure treated, R319.1 item 2
2. Specify any ledgers connected to masonry walls with 3x material, R606.11.
3. Show weep screeds with a minimum clearance 4" above grade or 2" above paved areas, R703.6.2.1. This may require a design with concrete stems.
4. Specify water-resistive barrier equivalent to two layers of Grade D paper over the wood based sheathing of exterior plaster wall coverings, R703.6.3.
5. Show location and method of flashing all wall and roof intersections, R903.2.1.
6. Provide roof scupper openings with a (4" min) width equal to the drain circumference required for the area served (3 in/hr rainfall rate), UPC 1101.11.2.1 & Table 11-1.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2006 Uniform Plumbing Code and 2006 International Residential Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference one of these codes for Plumbing.
2. Note and specify all piping materials (PVC, PEX, ABS), UPC 301.1.1. IRC P2608.
3. Provide pipe sizes (diameter & length), average pressure and a complete fixture unit schedule UPC 610.8, Table 6-6. IRC P2903.6. Existing water pipes may require replacement to larger sizes, UPC 610.8, Table 6-6. IRC P2903.7.
4. Clarify the point of connection of the new hot and cold water lines to existing service pipes. The supply pipes must be evaluated for sufficient size for controlling excessive flow rates, UPC 610.3..

MECHANICAL PLANS:

1. Show the location of exterior mounted HVAC equipment, M1302.1. Or, provide return air duct sizes, M1602. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN / 1000 BTU, M1403.1 (1 ton cooling = 12,000 BTU).
2. Show bathroom exhaust fan with minimum 50 CFM rating R303.3 and M1507.3

ELECTRICAL PLANS:

1. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3304.11 & E3606.2.
2. Show the location and capacity of the load center panel, E3501.6.2 & E3605.8.
3. Provide an electrical load calculation if the load center panel size is less than 200A, E3502.2.
4. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3603.5.
5. Show the Bathroom on a separate 20 AMP circuit (dedicated) with outlets at no other locations, E3603.4.
6. Note that combination type arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.12.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
2. Provide spec sheets for all full cut-off fixtures showing the lamp type, placement and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). Fixtures are only exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review