Permit Number: T09CM02071
Parcel: 110091740

Review Status: Active

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02071
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 9-02-09
Activity: T09CM02071
Address: 2872 N. Magnolia Ave
Applicant: Charley Anderson

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

FLOOR PLANS:
2. Identify ceiling heights in all areas. Note average height at sloped ceiling areas, R305.1.

FOUNDATION PLANS:
3. Specify size of point-load footings under carport posts, R401.2.

STRUCTURAL PLANS:
4. Provide adequate holdown hardware for alternate braced wall panels (ratings for PAHD42 is inadequate, HD2A is no longer in production) R602.10.6.
5. Specify the size and spacing of proposed ceiling joists, R801.2.
6. Specify size of all structural headers over doors and windows, R801.2.

MECHANICAL PLAN:
7. Correct air conditioning note number 1 to apply to City of Tucson amendments.
8. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, R1103.2.1.

ELECTRICAL PLAN:
9. Show locations of smoke detectors (every sleeping room and hallways leading to). All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R313.

OUTDOOR LIGHTING CODE
10. Provide an accurate outdoor lighting calculation, OLC 3.1.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status