Permit Number: T09CM02064
Parcel: 135042150

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM02064
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the listing information for the solar collectors and the drainback tank. reference: section 1404.1, IMC 2006.
2. If the solar collectors and drainback tank are not listed for use with potable water, show that the heat exchanger is certified for cross contamination prevention.
3. Clarify the required pressure (and temperature?) relief settings for the solar collectors and the drainback tank.