Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T09CM02064
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the listing information for the solar collectors and the drainback tank. reference: section 1404.1, IMC 2006. 2. If the solar collectors and drainback tank are not listed for use with potable water, show that the heat exchanger is certified for cross contamination prevention. 3. Clarify the required pressure (and temperature?) relief settings for the solar collectors and the drainback tank. |