Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02063
Parcel: 10818716A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02063
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2009 GERRY KOZIOL WWM REVIEW Approved
08/11/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE STRUCTURAL CALCULATIONS INDICATING THE EXISTING ROOF STRUCTURE CAN ADEQUATELY SUPPORT THE NEW/REPLACEMENT AC UNITS (AS LISTED ON SHEET M1.1 IN THE 'AIR BALANCE SCHEDULE' AND 'KEY NOTES').
2. SHEET A5.0; BREAK ROOM ELEVATIONS: VERIFY THAT COUNTER/SINK HEIGHTS IN THE BREAK ROOM MEET ACCESSIBILITY REQUIREMENTS.
08/12/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied SEE BUILDING COMMENTS.
08/17/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved 1. The City of Tucson is currently under the 2006 UPC.
08/17/2009 RMYERS1 WATER REVIEW Approved
08/17/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations to take into account the different occupancy loads in the project space. Reference: Sections 403.3 and 403.3.2, IMC 2006.
2. If the new rooftop AC units (AC 6-2 and AC 6-3) have a different natural gas input than the units that are being replaced, provide the revised natural gas pipe sizes and piping layout. Include gas pressures and developed pipe lengths on plans. Reference: Section 1217.0, UPC 2006.
08/26/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2009 CPIERCE1 OUT TO CUSTOMER Completed
08/26/2009 SUE REEVES REJECT SHELF Completed