Permit Number: T09CM02043
Parcel: 141153530

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02043
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1; SHEET A-2: DETAILS 6 AND 9 DO NOT MEET MINIMUM 3/32" LETTERING REQUIREMENTS.
2. PREVIOUS COMMENT 3; SHEET T-1: VB CONSTRUCTION IS STILL INDICATED UNDER THE HEADINGS "CONSTRUCTION TYPE" AND "ALLOWABLE BUILDING AREA". CONFIRM THIS IS II-B CONSTRUCTION, AND CHANGE ON DRAWINGS.
3. PREVIOUS 4; DETAIL 6/A-3: DETAIL 6 DOES NOT INDICATE THE CONNECTION SIZE AND QUANTITY OF THE BRACING TO THE TOP OF THE PARTITION, OR TO THE ROOF STRUCTURE ABOVE. DETAIL 4 IS FOR AN INTERIOR PARTITION THAT RUNS FULL HEIGHT TO THE ROOF STRUCTURE, WHICH IS DIFFERENT THAN DETAIL 6. CLARIFY.
4. PREVIOUS 6; DETAIL 13/A-3: WHERE THE SOFFIT IS PARALLEL TO THE JOISTS, THE 6X4 STEEL ANGLE NOTE SHOULD NOT BE "BETWEEN JOISTS". CLARIFY.
5. SHEET A-3; RESPONSE TO REVIEW COMMENTS: THE COMMENT THAT DETAIL 19 IS REVISED AND DETAIL 9 IS COORDINATED WITH DETAIL 19 IS UNCLEAR. THERE IS NO DETAIL 19 ON THIS SHEET.
09/25/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review .

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2009 DELMA ROBEY OUT TO CUSTOMER Completed