Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02043
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 1; SHEET A-2: DETAILS 6 AND 9 DO NOT MEET MINIMUM 3/32" LETTERING REQUIREMENTS. 2. PREVIOUS COMMENT 3; SHEET T-1: VB CONSTRUCTION IS STILL INDICATED UNDER THE HEADINGS "CONSTRUCTION TYPE" AND "ALLOWABLE BUILDING AREA". CONFIRM THIS IS II-B CONSTRUCTION, AND CHANGE ON DRAWINGS. 3. PREVIOUS 4; DETAIL 6/A-3: DETAIL 6 DOES NOT INDICATE THE CONNECTION SIZE AND QUANTITY OF THE BRACING TO THE TOP OF THE PARTITION, OR TO THE ROOF STRUCTURE ABOVE. DETAIL 4 IS FOR AN INTERIOR PARTITION THAT RUNS FULL HEIGHT TO THE ROOF STRUCTURE, WHICH IS DIFFERENT THAN DETAIL 6. CLARIFY. 4. PREVIOUS 6; DETAIL 13/A-3: WHERE THE SOFFIT IS PARALLEL TO THE JOISTS, THE 6X4 STEEL ANGLE NOTE SHOULD NOT BE "BETWEEN JOISTS". CLARIFY. 5. SHEET A-3; RESPONSE TO REVIEW COMMENTS: THE COMMENT THAT DETAIL 19 IS REVISED AND DETAIL 9 IS COORDINATED WITH DETAIL 19 IS UNCLEAR. THERE IS NO DETAIL 19 ON THIS SHEET. |
| 09/25/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | . |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/28/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |