Permit Number: T09CM02043
Parcel: 141153530

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02043
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2009 DAVE MANN FIRE REVIEW Approved
08/03/2009 GERRY KOZIOL WWM REVIEW Approved
08/06/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: A MINIMUM 3/32" LETTERING HEIGHT IS REQUIRED ON ALL DRAWINGS. PROVIDE.
2. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED BY LEERAY HANLY.
3. SHEET T-1; PROJECT DATA: PER THE 2006 IBC SECTION 507.3, THE ALLOWABLE AREA OF A SPRINKLERED GROUP M BUILDING SHALL NOT BE LIMITED FOR CONSTRUCTION OTHER THAN TYPE V. UNDER THE PROJECT DATA, TYPE V CONSTRUCTION IS LISTED. CLARIFY.
4. SHEET A-3; DETAIL 6: AT THE DIAGONAL BRACING, PROVIDE CONNECTION SIZE AND QUANTITY AT THE TOP OF THE PARTITION, AND TO THE STRUCTURE ABOVE.
5. SHEET A-3; DETAIL 13: PROVIDE STRUCTURAL CALCULATIONS FOR THE NEW SOFFIT FRAMING AND CONNECTIONS.
6. SHEET A-3; DETAIL 13: WHERE THE SOFFIT IS PARALLEL TO THE JOISTS, THE 6X4 STEEL ANGLE NOTE SHOULD NOT BE "BETWEEN JOISTS". CLARIFY.
08/06/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
08/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide direct waste connections for the wash and rinse sections of the 3-compartment sinks, with an indirect connection for the sanitizing compartments (or compartments that come in direct contact with ready-to-eat food) only. Reference: Sections 304.0 and 801.2.3, UPC 2006.
2. Fixtures that rough in above the floor (e.g. PLHSW hand sink) are not permitted to be included in a combination waste and vent system. Reference: Section 910.5, UPC 2006.
3. Relocate the reduced pressure backflow preventer for the sanitizer serving the 3-compartment sink to conform to the access and clearance requirements of Section 603.3.4, UPC 2006.
08/13/2009 ROBERT SHERRY WATER REVIEW Approved
08/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/17/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2009 DELMA ROBEY OUT TO CUSTOMER Completed
08/19/2009 SUE REEVES REJECT SHELF Completed