Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02043
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/03/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 08/06/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: A MINIMUM 3/32" LETTERING HEIGHT IS REQUIRED ON ALL DRAWINGS. PROVIDE. 2. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED BY LEERAY HANLY. 3. SHEET T-1; PROJECT DATA: PER THE 2006 IBC SECTION 507.3, THE ALLOWABLE AREA OF A SPRINKLERED GROUP M BUILDING SHALL NOT BE LIMITED FOR CONSTRUCTION OTHER THAN TYPE V. UNDER THE PROJECT DATA, TYPE V CONSTRUCTION IS LISTED. CLARIFY. 4. SHEET A-3; DETAIL 6: AT THE DIAGONAL BRACING, PROVIDE CONNECTION SIZE AND QUANTITY AT THE TOP OF THE PARTITION, AND TO THE STRUCTURE ABOVE. 5. SHEET A-3; DETAIL 13: PROVIDE STRUCTURAL CALCULATIONS FOR THE NEW SOFFIT FRAMING AND CONNECTIONS. 6. SHEET A-3; DETAIL 13: WHERE THE SOFFIT IS PARALLEL TO THE JOISTS, THE 6X4 STEEL ANGLE NOTE SHOULD NOT BE "BETWEEN JOISTS". CLARIFY. |
| 08/06/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 08/13/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide direct waste connections for the wash and rinse sections of the 3-compartment sinks, with an indirect connection for the sanitizing compartments (or compartments that come in direct contact with ready-to-eat food) only. Reference: Sections 304.0 and 801.2.3, UPC 2006. 2. Fixtures that rough in above the floor (e.g. PLHSW hand sink) are not permitted to be included in a combination waste and vent system. Reference: Section 910.5, UPC 2006. 3. Relocate the reduced pressure backflow preventer for the sanitizer serving the 3-compartment sink to conform to the access and clearance requirements of Section 603.3.4, UPC 2006. |
| 08/13/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/13/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/17/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/19/2009 | SUE REEVES | REJECT SHELF | Completed |