Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02037
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 08/06/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: A MINIMUM OF 3/32" LETTERING IS REQUIRED ON ALL SHEETS. 2. SHEET a1.0; GENERAL BUILDING SUMMARY: THE OCCUPANCY BREAKDOWN LISTS 29 TOTAL OCCUPANTS, WHILE THE RESTROOM CALCULATION BREAKDOWN LISTS 4.62 OCCUPANTS. COORDINATE AND CLARIFY. REFER TO THE 2006 IBC SECTION 2902.2(3) FOR SEPARATE FACILITIES. 3. SHEET a2; PLANS: REMOVE WHEELCHAIR TURNING CIRCLES IN RESTROOMS 106 AND 107. THESE RESTROOMS DO NOT MEET ICC/ANSI A117.1-2003 REQUIREMENTS FOR ACCESSIBILITY. 4. SHEET a2; WALL TYPES: WALL TYPE 'A' INDICATES STRUCTURAL DRAWINGS (THERE ARE NONE) AND BRACING OF THE WALL TO THE ROOF PER DETAIL 1/a9.0 (THERE IS NO a9.0). CLARIFY THIS NOTE, AND PROVIDE THE BRACING DETAIL, INDICATING THE BRACE SIZE AND SPACING, ALONG WITH THE CONNECTION SIZE AND QUANTITY OF THE BRACE TO THE PARTITION WALL AND TO THE ROOF STRUCTURE ABOVE. 5. GENERAL: PROVIDE A BREAKDOWN OF PROJECT COSTS, INCLUDING THE 20% MAXIMUM FOR ACCESSIBILITY ISSUES PER THE IBC SECTION 3409.7. INCLUDE THIS ON THE DRAWINGS. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/07/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 08/13/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. 2. Plumbing General Note #1 indicates that "all plumbing to remain the same" but sheet A2 calls for at least one new hand sink. Clarify. Reference: Section 103.2.3, UPC 2006. 3. Provide fixture descriptions for all new plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, NSF, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006. 4. Appliances (e.g. ovens, ice makers, coffee makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. 5. Whether a grease interceptor is required or not is determined by the Pima County Industrial Wastewater Control Department. Provide a letter from the Pima County Industrial Wastewater Control Department confirming that a grease interceptor is not required. Reference: Sections 103.2.3 and 1009.1, UPC 2006. |
| 08/13/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/13/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.3.1, IBC 2006. 2. Provide the manufacturer's listing for the proposed oven (equipment #25). Reference: Section 103.5, IMC 2006. 3. Show that the heat output of the oven is accounted for in the HVAC design. Reference: Section 507.2.2, IMC 2006. 4. Mechanical Distribution General Note #1 calls for the HVAC system to be balanced. Provide balancing information. Reference: Section 106.3.1, IBC 2006. 5. Mechanical Distribution General Note #2 indicates that the existing ductwork has been "only slightly modified". Show the extent of the modification. Reference: Section 106.3.1, IBC 2006. |
| 08/21/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |