Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T09CM02027
Review Name: RESUBMITTAL
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2009 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
| 10/15/2009 | Any | ZONING HC | REVIEW | Active | |
| 10/15/2009 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Active | |
| 10/16/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project with a demand of 15 GPM. |
| 10/16/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/19/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The existing 6"x 6" scupper is undersized. The effective roof area of 1035 square feet requires a 3" roof drain or a minimum scupper width of 9.4". Reference: Sections 103.2.3 and 1101.11.2.1, UPC 2006. |