Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM02027
Parcel: 13215005A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02027
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2009 GERRY KOZIOL WWM REVIEW Approved
07/30/2009 DAVE MANN FIRE REVIEW Approved
08/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: SUITE 'C' (ALTHOUGH NOT PART OF THIS TI) DOES HAVE WORK BEING PERFORMED (INFILL OF 3 EXISTING WINDOWS) THAT SHOULD BE INCLUDED AS PART OF PROJECT T09CM02027, AND A VALUATION AMOUNT ADDED. VERIFY.
08/05/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
08/07/2009 RMYERS1 WATER REVIEW Denied 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Include the demand due to the three evaporative coolers in addition to the plumbing fixtures. Reference: Sections 610.1 and 610.2, UPC 2006.
2. Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Show the size and location of the reduced pressure backflow prevention assembly on the drawing. Reference: Section 103.2.3, UPC 2006 and COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
08/10/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify suite number. Suite #100 has already been reviewed as suite "A" unit #170. Any other unit in building one still needs review.
2. Show how the storm water is being drained from the roof of the existing office area. Reference: Sections 103.2.3 and 1101.11.1, UPC 2006.
08/12/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments under T09CM02021 per Ray T Majuta,8/22/09
08/26/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Cupps Industrial Supply
T09CM02020, T09CM02021, T09CM02023, T09CM02027
Building Plan (1st Review)

TRANSMITTAL DATE: August 26, 2009

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm02020.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
08/26/2009 SUE REEVES REJECT SHELF Completed