Permit Number: T09CM02026
Parcel: 12809006B

Address:
5443 E 22ND ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM02026
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify how the 10 GPM external flow control device will work with the specified hydromechanical grease interceptor which includes an integral flow control and is rated for 20 GPM. Reference: Sections 103.2.3 and 310.4, UPC 2006.
2. Resize the section of the gas piping between G2 and G3; 418 CFH at 250 feet requires a 2" pipe. Reference: Table 402.4(2), IFGC 2006.
11/03/2009 GERRY KOZIOL WWM REVIEW Passed
11/06/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/12/2009 DELMA ROBEY OUT TO CUSTOMER Completed
11/12/2009 SUE REEVES REJECT SHELF Completed