Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify how the 10 GPM external flow control device will work with the specified hydromechanical grease interceptor which includes an integral flow control and is rated for 20 GPM. Reference: Sections 103.2.3 and 310.4, UPC 2006. 2. Resize the section of the gas piping between G2 and G3; 418 CFH at 250 feet requires a 2" pipe. Reference: Table 402.4(2), IFGC 2006. |
11/03/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
11/06/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |