Permit Number: T09CM02026
Parcel: 12809006B

Address:
5443 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02026
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2009 STEVE SHIELDS ZONING REVIEW Approved
07/29/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/30/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information regarding the existing hood to show that it has the capacity to accomodate the proposed new equipment.
07/30/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE DETAIL INDICATING BRACING OF TOP OF PARTITION WALLS (SEE PARTITION TYPE 4A). INCLUDE BRACING SIZE AND SPACING, AND CONNECTION OF BRACE TO EXISTING STRUCTURE AND TOP OF PARTITION.
07/30/2009 ROBERT SHERRY WATER REVIEW Approved
07/30/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If the hand sink is to be connected to the existing grease interceptor, provide a readily accessible, vented flow control device for the hand sink.
2. Confirm that the existing grease interceptor has the capacity to take on the additional flow from the hand sink
3. Provide a waste and vent riser diagram for the new work and show how the new piping relates to the existing piping.
4. Verify that the sanitizing compartment of the 3-compartment sink is indirectly wasted.
5. Provide the size of the section of gas piping between the 3/4" branch serving the water heater and the connection to the 2-1/2" gas main.
6. Clarify the routing of the new 2-1/2" gas main.
07/30/2009 DAVE MANN FIRE REVIEW Approved
07/30/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
07/30/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/30/2009 RONALD BROWN ADA REVIEW Passed
08/04/2009 THAUSER1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2009 THAUSER1 OUT TO CUSTOMER Completed