Permit Number: T09CM02019
Parcel: 127021720

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02019
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2009 GERRY KOZIOL WWM REVIEW Approved
08/25/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM02019

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007; the 2006 UPC with amendments on 7/10/2007; effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson on 10/16/2007. Notate accessible route, door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
2. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation with one of the following provisions: control and ¾" piping for water with rooftop termination; 3" metallic sleeve; or an accessible attic over the water heater.
3. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation. 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic".

STRUCTURAL PLANS:

1. Show the rooftop HVAC weight (381 lbs) on the Framing Plan sheet #1. Engineered trusses may require an engineer analysis for verifying the load carrying capacity for the additional load, M1401.

SECTIONS - DETAILS:

1. Clarify the detail reference sheet numbers appearing on sheet #1, R106.1.1.
2. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
3. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2. Clarify the second note block on sheet #2.
4. The installation of a fiber glass shingle on roof surfaces over unvented attic space may void the manufacturer's warranty. Show compliance with R806 by providing tile, metal or built-up covering, or show the shingle manufacturer's requirement.

PLUMBING PLANS:

1. Show the (indoor rated) water heater with outdoor protection, IRC G2406.3.
2. Provide a gas plan showing the point of connection and size the supply pipe for the connected demand. Revise the (18') total developed length showing a length from the meter to the most remote appliance on the system. IRC Table G2413.4(1). The gas pipe supplying both dwellings may require upgrading.

MECHANICAL PLANS:

1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended).

ELECTRICAL PLANS:

1. Provide a panel schedule showing each circuit numbers with general description, E3304.11 & E3606.2. Add the roof mounted HVAC circuits.
2. Show Bathroom receptacles on a separate 20 AMP circuit (#17) with outlets at no other locations (bedroom), E3603.4.
3. Peninsular counter tops shall have at least one receptacle outlet within 12" below the countertop surface, E3801.4.2 and E3801.4.3. The countertop may not extend more than 6" beyond the receptacle surface, E3801.4.5 Except.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
2. Provide spec sheets for all full cut-off fixtures showing the lamp type, placement and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). Fixtures are only exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/28/2009 CPIERCE1 OUT TO CUSTOMER Completed
08/28/2009 SUE REEVES REJECT SHELF Completed