Permit Number: T09CM02006
Parcel: 11108175F

Address:
3749 E GRANT RD

Review Status: Completed

Review Details: SITE

Permit Number - T09CM02006
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2009 DAVE MANN FIRE REVIEW Approved
10/05/2009 RBROWN1 ADA REVIEW Passed Not a COT owned/operated property
10/07/2009 STEVE SHIELDS ZONING REVIEW Denied PLANNING AND DEVELOPMENT SERVICES DEPARTMENT TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Duran Business Center
T09CM02006
Site Plan (1st Review)

TRANSMITTAL DATE: October 8, 2009

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the area of expansion only.

2. Add a note stating that the project is designed to meet the overlay zone criteria: Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone; Sec.

3. D.S. 2-02.2.1.A.8 As it appears that a new sidewalk is proposed and the proposed sidewalk is only 5'-0" wide wheel stops area required for all vehicle parking spaces adjacent to the sidewalk. Provide a fully dimensioned vehicle parking spaces detail that shows the location of the wheel stop, see D.S. 3-05.2.3.C.2 and Figure 5.

4. D.S. 2-02.2.1.A.9 Per LUC Section 3.3.3.5 Bicycle Parking Requirements. The number of required bicycle parking spaces is calculated as a percentage of the total number of motor vehicle parking spaces provided. If the calculated number of required bicycle parking spaces is less than two (2), the minimum number of required spaces is two (2). Also per LUC Section 3.3.7.8.A Any use providing less than fifty (50) motor vehicle parking spaces may substitute Class 2 spaces for Class 1 spaces. Provide a detail for the required Class 2 bicycle parking, including materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports. For your information a single inverted "U" style bicycle rack can support two (2) bicycle racks.

5. D.S. 2-02.2.1.A.9 The location of the "BICYCLE RACK" encroaches into a required sidewalk.

6. D.S. 2-02.2.1.A.10 Show existing and future sight visibility triangles (SVT's) on the plan.

7. D.S. 2-02.2.1.A.12 As it appears that a new sidewalk is proposed, the sidewalk must meet the requirements of D.S. 2-08.4.1. Demonstrate on the plan how the accessible access aisle will gain access to the sidewalk.

8. D.S. 2-02.2.1.A.13 Provide the type, size and height for the existing sign shown on the plan.

9. D.S. 2-02.2.1.A.18 Label Grant Road as an MS&R.

10. D.S. 2-02.2.1.A.19 Provide the future right-of-way (ROW) on the plan.
11. D.S. 2-02.2.1.A.25 If applicable show the existing and/or proposed site lighting on the plan.

12. D.S. 2-02.2.1.A.28 The zoning shown south of Grant Road is not correct. This zoning should be listed as C-2.

13. D.S. 2-02.2.1.A.31 Provide the subject to section for the proposed use on the plan. The proposed use should be listed as "ADMINSTRATIVE AND PROFESSIONAL OFFICE "31", SUBJECT TO: SEC. 3.5.13.5

14. D.S. 2-02.2.2.A.3 The floor area ration (FAR) calculation should show the Allowed FAR = 24,780, Proposed FAR = 1,378

15. D.S. 2-02.2.2.A.4 The vehicle parking calculation is not correct. Base on a use of ADMINSTRATIVE AND PROFESSIONAL OFFICE the ratio used is one (1) vehicle parking space per 200 sq. ft. of gross floor area. Revise the calculation to show the correct ratio and the required number should be 7 with 9 provided.

16. D.S. 2-02.2.2.A.4 The bicycle parking calculation is not correct, see comment #4 above. The calculation should show 2 required and 2 provided.

17. Depending on how the above comments are addressed addition comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t09cm02006

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
10/09/2009 ANDREW CONNOR NPPO REVIEW Passed
10/09/2009 ANDREW CONNOR LANDSCAPE REVIEW Denied According to the previously approved site plan dated 12/28/1976 a chain link fence w 1-1/2' slats is to be installed on the N. property line. Identify screening element on submitted site plan.
10/13/2009 LOREN MAKUS ENGINEERING REVIEW Denied October 20, 2009
T09CM02006

Address the following:

1. Site PlanClarify extent of existing pavement and delineate any addition pavement proposed.
2. Show enough of adjacent properties to show separations between existing driveways.
3. Delineate to the extent possible the proposed alignment for Grant Road and show how this site will be able to function after the additional right-of-way is taken.
4. The property is shown as 112.85 ft wide on the submitted site plan, and 112.15 on the previously approved plan and on the Assessor's map. Correct the discrepancy.
5. The previously approved site plan shows a shared driveway with the property to the east. The newer configuration doesn't comply with the Traffic Access Management Guidelines. Provide documentation of prior approval for the revised access or provide approval from the City of Tucson Department of Transportation for the existing access.

Loren Makus
loren.makus@tucsonaz.gov
10/26/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location and size of the public sanitary sewer and
d. the location, invert, and rim elevation of all manholes
e. the finished floor elevation of the building
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
04/01/2010 SUE REEVES REJECT SHELF Completed