Permit Number: T09CM01998
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM01998
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2009 MARTIN BROWN FIRE REVIEW Approved
08/13/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S4.01; DETAIL 20: DID NOT LOCATE SHAFT DIAMETER ON DRAWINGS, OR "DRILLED PIER SCHEDULE" AS REFERENCED IN NOTE 2. PROVIDE.
2. SHEET S5.01; SECTIONS 8 AND 9: PROVIDE THE THICKNESS OF THE FOOTING (OR A REFERENCE TO A NOTE/DETAIL). DID NOT LOCATE THE FOOTING SIZE INDICATED IN THE CALCULATION ON PAGE 402.
3. SHEET S5.01; SECTIONS 8 AND 9: PROVIDE THE THICKNESS OF THE WALL (OR A REFERENCE TO A NOTE/DETAIL). THE CALCULATIONS INDICATE AN 8" WALL.
4. CALCULATIONS: DID NOT LOCATE THE CALCULATIONS FOR THE SPREAD FOOTINGS F2, F3, F4, AND F5. PROVIDE ALONG WITH THE GRID LOCATION OF EACH FOOTING DESIGN.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/14/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
08/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/14/2009 ROBERT SHERRY WATER REVIEW Approved
08/14/2009 RSHERRY1 WWM REVIEW Passed No new wastewater-connected fixtures
08/19/2009 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 08/19/2009,

The Development Package and the Drainage Report have not been approved by Engineering yet.
08/19/2009 PATRICIA GEHLEN ZONING REVIEW Denied Plans may not be approved until the development plan is aprpoved.
08/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:260 N Church, T09CM01998
Foundation and Demo

The Electrical Plans for this project have been denied for the following:


1 . Sheet ES.1 Legend Note #2 indicates that the new 13.8 KV feeder be replaced to match existing, please indicate exactly the type of conductor is to be used, insulation type and voltage. A description should be given for installer to use and inspector to verify rather than attempt to match existing properties.
2. Provide information on type of splice kit to be used as per Legend Note #4 on Sheet ES.1.
3. Sheet ES.1 note indicates on Legend Note #10 that branch circuits for site lighting back to Panel 1HEE, list size conduit, conductor and number, and location of Panel 1Hee.
4. Sheet E2.2 shows a new 480 volt line, is this part of this project, if so where does it come from and where does it go ?


Ray T Majuta
Elect Pln Ck
PDS City of Tucson
8/24/09
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2009 CPIERCE1 OUT TO CUSTOMER Completed