Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01993
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/27/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 07/27/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 07/27/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/27/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 07/27/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/06/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/06/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/06/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/06/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a design for mounting the shelf for the water heater to the wall. Provide structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 2. Show the easements for the existing building sewer. If additional buildings are connected to the sewer, provide a recorded joint sewer use agreement. |
| 10/13/2009 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 10/13/2009 | DROBEY1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2009 | DELMA ROBEY | OUT TO CUSTOMER | Needs Review |
| 10/13/2009 | DELMA ROBEY | REJECT SHELF | Needs Review |
| 10/13/2009 | DELMA ROBEY | APPROVAL SHELF | Needs Review |