Permit Number: T09CM01993
Parcel: 12112399J

Address:
5302 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01993
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2009 TERRY STEVENS ZONING REVIEW Approved
07/27/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/27/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
07/27/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/27/2009 ERIC NEWCOMB ADA REVIEW Passed
07/27/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/06/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
08/06/2009 ROBERT SHERRY WATER REVIEW Approved
08/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for mounting the shelf for the water heater to the wall. Provide structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Show the easements for the existing building sewer. If additional buildings are connected to the sewer, provide a recorded joint sewer use agreement.
10/13/2009 DROBEY1 WWM REVIEW Needs Review
10/13/2009 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2009 DELMA ROBEY OUT TO CUSTOMER Needs Review
10/13/2009 DELMA ROBEY REJECT SHELF Needs Review
10/13/2009 DELMA ROBEY APPROVAL SHELF Needs Review