Permit Number: T09CM01981
Parcel: 21439022B

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM01981
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2009 DAVE MANN FIRE REVIEW Approved
07/30/2009 GERRY KOZIOL WWM REVIEW Passed
08/03/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 12; TANK: PROVIDE STRUCTURAL CALCULATIONS FOR THE TANK FOUNDATION.
2. SHEET 14; CONTROL BUILDING: PROVIDE STRUCTURAL CALCULATIONS FOR THE CONTROL BUILDING.
3. SHEET 17; TANK: PROVIDE STRUCTURAL CALCULATIONS FOR THE TANK FOUNDATION.
4. SHEET 17; STEEL WATER TANK NOTE 3: IF THE MANUFACTURER LOADS ARE ACCEPTED BY THE NEXT REVIEW, REMOVE THIS NOTE.
5. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED BY THE BUILDING OFFICIAL.
08/04/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/04/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
08/10/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/10/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/10/2009 ROBERT SHERRY WATER REVIEW Passed
08/13/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM1981, City of Tucson Water
Booster Station
4300 N Broken Springs Tr

The Electrical Plans have been denied for the following:

1. Sheet 21, the feeders from the 200 Amp Main disconnect to the wireway shows only 2-4/0 's and 1#6 grd, the neutral or grounded conductor is missing.
2. The starters on this sheet (21) appear to be for a 3 phase system,the system is only single phase.
3. The main disconnect for the Air Compressor and Booster Pumps show a single phase system being connected, shown are starters for a 3 phase system, explain note 22 on this page (21).
4. Since there is no neutral or grounded to the wireway, the same is missing to the Control Panel.



Ray T Majuta
City of Tucson, PDS
Elect Plan Ck
8/17/09
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/18/2009 THAUSER1 OUT TO CUSTOMER Completed
08/18/2009 SUE REEVES REJECT SHELF Completed