Permit Number: T09CM01971
Parcel: 12620001C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01971
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2009 DAVID RIVERA ZONING REVIEW Approved
07/23/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/23/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
07/23/2009 ROBERT SHERRY WATER REVIEW Passed
07/23/2009 ARMANDO QUIROZ BUILDING-COMMERCIAL REVIEW Denied 1. Please provide additional detailing for the roofing structure over the stage, elevations and structural calculations. Please define more clearly the existing and new construction elements.
07/23/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
07/23/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/23/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/23/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/23/2009 ARMANDO QUIROZ ZONING HC SITE REVIEW Passed Reference ADA, this is a COT owned/operated property
07/23/2009 ARMANDO QUIROZ ADA REVIEW Denied 1. Define accessibility as per ADAAG to the stage.
2. A maximum of 20% needs to allocated to accessibility as per 2006 IBC, Section 3409.7.1. Please define cost breakdown and summary on drawings.
3. Please provide for accessible seating as per ADAAG.
07/29/2009 CPIERCE1 FIRE REVIEW Needs Review