Permit Number: T09CM01948
Parcel: 140420300

Address:
6970 S TUCSON BL

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM01948
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PER THE IBC SECTION 406.1.2, A GROUP U OPEN GARAGE IS LIMITED TO 3000 SF PER UNIT. MORE THAN 3000 SF SHALL BE PERMITTED, PROVIDED EACH 3000 SF AREA IS SEPARATED BY FIRE WALLS OR A 10' CLEAR DISTANCE. VERIFY.
2. GENERAL: THE DISTANCE FROM THE EDGE OF THE CANTILEVERED ROOF/DECK MUST FOLLOW REQUIREMENTS OF THE IBC, SECTION 704.2(1). THIS STATES THAT THE PROJECTION SHALL NOT EXTEND BEYOND A POINT ONE-THIRD THE DISTANCE FROM AN ASSUMED VERTICAL PLANE (PER TABLE 602, THIS DISTANCE IS 5') TO THE PROPERTY LINE. THE EDGE OF THE CANOPY/DECK CAN THEREFORE BE 5/3=1'-8" MINIMUM DISTANCE FROM THE ASSUMED VERTICAL PLANE, OR MINIMUM 3'-4" FROM THE PROPERTY LINE. VERIFY.
08/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2009 THAUSER1 OUT TO CUSTOMER Completed
08/26/2009 SUE REEVES REJECT SHELF Completed