Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T09CM01948
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/30/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: PER THE IBC SECTION 406.1.2, A GROUP U OPEN GARAGE IS LIMITED TO 3000 SF PER UNIT. MORE THAN 3000 SF SHALL BE PERMITTED, PROVIDED EACH 3000 SF AREA IS SEPARATED BY FIRE WALLS OR A 10' CLEAR DISTANCE. VERIFY. 2. GENERAL: THE DISTANCE FROM THE EDGE OF THE CANTILEVERED ROOF/DECK MUST FOLLOW REQUIREMENTS OF THE IBC, SECTION 704.2(1). THIS STATES THAT THE PROJECTION SHALL NOT EXTEND BEYOND A POINT ONE-THIRD THE DISTANCE FROM AN ASSUMED VERTICAL PLANE (PER TABLE 602, THIS DISTANCE IS 5') TO THE PROPERTY LINE. THE EDGE OF THE CANOPY/DECK CAN THEREFORE BE 5/3=1'-8" MINIMUM DISTANCE FROM THE ASSUMED VERTICAL PLANE, OR MINIMUM 3'-4" FROM THE PROPERTY LINE. VERIFY. |
08/20/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/26/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |
08/26/2009 | SUE REEVES | REJECT SHELF | Completed |