Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM01937
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the space will be heated. The note in the Rooftop Unit Schedule calls for gas heat but no gas piping has been added to the project. Also, to heat 1500 CFM of outside air from 30 degrees F to 68 degrees F will require about 12 KW of heat. 2. If gas heat is to be used, revise the plumbing drawings to add the required gas piping. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/21/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |