Permit Number: T09CM01937
Parcel: 117120210

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01937
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The submitted structural calculations and description of the water heater platform are fine but the construction information included with the calculations needs to be included on the drawing. Reference: Sections 310.0 and 314.5, UPC 2006.
2. The submitted water supply calculations indicate that some of the water piping has been undersized (e.g. a 1" pipe serving over 18 fixture units, a ½" pipe serving over 1 fixture unit). Reference: Sections 610.4 and 610.5, UPC 2006.
3. Floor sinks and floor drains can't be connected to a hydromechanical grease interceptor because the external flow control device for a hydromechanical grease interceptor is required to be installed in a location that is readily accessible and visible. (Note that a sanitizing compartment is not normally connected to a hydromechanical grease interceptor.) Reference: Section 1014.2.1, UPC 2006.
4. A trap and a vent are required for all fixtures discharging into a grease interceptor. Reference: Section 1014.1.2, UPC 2006.
5. Show how the water-cooled ice maker (#17) conforms to Section 1201.3, IMC 2006 as amended by the City of Tucson
08/04/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2009 DELMA ROBEY OUT TO CUSTOMER Completed
08/06/2009 SUE REEVES REJECT SHELF Completed