Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T09CM01937
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/24/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/24/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/24/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/29/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the plumbing fixtures and drainage fittings (e.g. the traps and vents in the waste isometric) installed correctly and in a manner consistent with the Code and the manufacturer's instructions. Reference: Sections 304.0 and 310.4, UPC 2006. 2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 3. Provide a CW shut off valve for the water heater. Reference: Section 605.2, UPC 2006. 4. An ASSE 1022 backflow preventer is not acceptable for protecting the water supply to a carbonator; provide an ASSE 1013 reduced pressure principle backflow preventer. Reference: Section 603.4.12, UPC 2006. 5. Provide calculations showing how the water supply piping has been sized. Complete the water piping isometric by showing all of the pipe sizes. Reference: Sections 610.4 and 610.5, UPC 2006. 6. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0 and 801.2.3, UPC 2006. 7. Clarify the installation of the hydromechanical grease interceptor to show that it complies with the requirements of Section 1014.0 and the manufacturer's listing information. Specifically, show the locations of the flow control devices and their vents, cleanouts, and plumbing vents. Note that the specified interceptor has one inlet and one outlet. |
| 07/29/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the specified rooftop A/C unit is capable of maintaining a minimum temperature of 68 degrees F in the interior spaces intended for occupancy on a design heating day (32 degrees F). Reference: Sections 309.1 and 312.1, IMC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/03/2009 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 08/03/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/03/2009 | DELMA ROBEY | REJECT SHELF | Completed |