Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01937
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2009 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/21/2009 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 07/21/2009 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/21/2009 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT: TO9CMN01937 63 W WCONGRESS THE ELECTRICAL PLANS HAVE DENIED FOR THE FOLLOWING; 1. NO REQUIRED DISCONNECT MEANS AT METER ? 2. PROVIDE A GROUNDING DIAGRAM FOR THE NEW SERVICE. 3.IS THIS AN EXISTING OVERHEAD OR UNDERGROUND SERVICE? 4.VARIOUS SERVICES IN THIS LOCATION ARE 120/240V 3 PHASE WITH A HIGH LEG AS PER TEP, PLEASE VERIFY THAT THIS SERVICE IS A 120/208 V 3 PHASE, NOT A 120/240V 3 PHASE. 5.THE BRANCH CIRCUIT FEEDING THE RTU IS IMPROPERLY SIZED. 6. CIRCUIT A-23 IS USED TWICE ON A SINGLE RECEPTACLE AND ALSO ON THR OVEN PROOFER AS A PART OF A 3 PHASE CIRCUIT. 7. PROVIDE THE FAULT CURRENT AVAILABLE AT THE SERVICE FROM TEP. RAY T MAJUTA DSD CITY OF TUCSON ELECTRICAL PLAN CHECK 7/21/09, 520-837-4988 |
| 07/22/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Address the comment from 07/21/09. An appeal to the building official is required if using the International Plumbing Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/24/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 07/24/2009 | SUE REEVES | REJECT SHELF | Completed |