Permit Number: T09CM01937
Parcel: 117120210

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01937
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2009 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
07/21/2009 CPIERCE1 WWM REVIEW Needs Review
07/21/2009 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
07/21/2009 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: TO9CMN01937
63 W WCONGRESS


THE ELECTRICAL PLANS HAVE DENIED FOR THE FOLLOWING;
1. NO REQUIRED DISCONNECT MEANS AT METER ?
2. PROVIDE A GROUNDING DIAGRAM FOR THE NEW SERVICE.
3.IS THIS AN EXISTING OVERHEAD OR UNDERGROUND SERVICE?
4.VARIOUS SERVICES IN THIS LOCATION ARE 120/240V 3 PHASE WITH A HIGH LEG AS PER TEP, PLEASE VERIFY THAT THIS SERVICE IS A 120/208 V 3 PHASE, NOT A 120/240V 3 PHASE.
5.THE BRANCH CIRCUIT FEEDING THE RTU IS IMPROPERLY SIZED.
6. CIRCUIT A-23 IS USED TWICE ON A SINGLE RECEPTACLE AND ALSO ON THR OVEN PROOFER AS A PART OF A 3 PHASE CIRCUIT.
7. PROVIDE THE FAULT CURRENT AVAILABLE AT THE SERVICE FROM TEP.

RAY T MAJUTA
DSD CITY OF TUCSON
ELECTRICAL PLAN CHECK
7/21/09, 520-837-4988
07/22/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Address the comment from 07/21/09. An appeal to the building official is required if using the International Plumbing Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/24/2009 DELMA ROBEY OUT TO CUSTOMER Completed
07/24/2009 SUE REEVES REJECT SHELF Completed