Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01937
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/21/2009 | JIM MILITELLO | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide outside air calculations. Complete the rooftop unit capacity schedule. Provide method for providing makeup air to restrooms i.e. undercut door. |
| 07/21/2009 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/21/2009 | JMILITE1 | WATER | REVIEW | Approved | |
| 07/21/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Minimum lettering font size is 3/32" Change all fonts that are smaller than that including schedules. 2. Change toilet reference on sheet A1.1 to A/A-4. 3. At Detail A/A-4 put plan to 3/8" scale and show all critical accessible dimensions required by ICC/ANSI 117.1. 4. A-2 Occupancy classification does not work for one exit, i.e. table 1019.2; Maximum travel distance of 75 feet. As per 303.1 the A occupancy may be changed to "B" business. With a sprinkler system, travel distance may be changed to 100'. Occupany of 44 may be maintained as per Section 1004.2. 5. Please provide last approved site plan. END OF REVIEW |
| 07/21/2009 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 07/21/2009 | JIM MILITELLO | PLUMBING-COMMERCIAL | REVIEW | Needs Review | An appeal to the building official is required if using the International Plumbing Code. |
| 07/21/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 07/21/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/21/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 07/21/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/21/2009 | RONALD BROWN | ADA | REVIEW | Passed | NOT A COT OWNED/OPERATED PROPERTY |