Permit Number: T09CM01937
Parcel: 117120210

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01937
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
07/21/2009 JIM MILITELLO MECHANICAL-COMMERCIAL REVIEW Denied Provide outside air calculations.
Complete the rooftop unit capacity schedule.
Provide method for providing makeup air to restrooms i.e. undercut door.
07/21/2009 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/21/2009 JMILITE1 WATER REVIEW Approved
07/21/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Minimum lettering font size is 3/32" Change all fonts that are smaller than that including schedules.
2. Change toilet reference on sheet A1.1 to A/A-4.
3. At Detail A/A-4 put plan to 3/8" scale and show all critical accessible dimensions required by ICC/ANSI 117.1.
4. A-2 Occupancy classification does not work for one exit, i.e. table 1019.2; Maximum travel distance of 75 feet. As per 303.1 the A occupancy may be changed to "B" business. With a sprinkler system, travel distance may be changed to 100'. Occupany of 44 may be maintained as per Section 1004.2.
5. Please provide last approved site plan.
END OF REVIEW
07/21/2009 CPIERCE1 WWM REVIEW Needs Review
07/21/2009 JIM MILITELLO PLUMBING-COMMERCIAL REVIEW Needs Review An appeal to the building official is required if using the International Plumbing Code.
07/21/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/21/2009 DAVE MANN FIRE REVIEW Approved
07/21/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
07/21/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/21/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY