Permit Number: T09CM01933
Parcel: 126180130

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01933
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM01933 Rev 8/7/09
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return TWO sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Provide manufacturer specification sheets for collector panels, inverter and mounting hardware. Highlight the selected model showing electrical or mounting characteristics.

STRUCTURAL PLANS:
1. The 4x8 beam are undersized for the supporting the additional dead load along with a 20 PSF live load. Provide a design for carrying the total roof loads, M1401.
NOTES / SPECIFICATIONS
1. Provide the exact wording and location for the "Photovoltaic System Disconnect" marking required by NEC 690.14 (C) (2).
2. Provide the exact wording and location for the Warning Sign required by NEC 690.17.
3. Provide the exact wording and location for the AC Modules "Vnom, HZnom, Pmax, Imax, Iprotection" marking required by NEC 690.52. Show values on proposed label.
4. Provide the location for the "backfed" circuit breaker in compliance with NEC 690.64 (B) (5).
5. Specify that the module interconnection (MC) connectors shall be marked for positive and negative polarity. Reference NEC 690.33 (A).
6. Specify that the module interconnection connectors are capable of interrupting the circuit current without danger to the operator, or marked: "Do Not Open Under Load." (Reference NEC 690.33 (E) and Handbook commentary.)

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
08/10/2009 MICHAEL ST. PAUL ZONING REVIEW Needs Review
08/14/2009 ELIZABETH EBERBACH ENGINEERING REVIEW Approved Due to floodplain constraints, any electrical panels or installed equipment may not be placed lower than 2-feet from adjacent highest ground elevation.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2009 THAUSER1 OUT TO CUSTOMER Completed
08/21/2009 SUE REEVES REJECT SHELF Completed