Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM01922
Parcel: 12108094E

Address:
1675 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01922
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
07/24/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/24/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/24/2009 JASON GREEN ENGINEERING REVIEW Approved
07/24/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/24/2009 GERRY KOZIOL WWM REVIEW Approved
07/24/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
07/24/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/19/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 1675 N Wilmot Rd, T09CM01922
CIRCLE K Remodel



The Electrical Plans have been denied for the following :

1. Sheet E-3, the feeder from the tap point to Panel R is according to note #8 -- 4#1's and 1#6 grd. The #1 conductor is approved for 130 amps, Panel R shows a main circuit
breaker of 100 amps, the load on this panel is 117 amps. The Panel Schedule shows a 150 amp circuit breaker. All of these figures contradict each other, needs correction.
2. Sheet E-1 circuits for water heater are shown as R1-18,20, should be 28,30.
3. Sheet E-1 shows note 28 to indicate a new power pole, label a circuit for this and indicate on panel schedule.
4. Sheet E-1, cannot locate R1-10-12, for ice maker B as shown on panel schedule.
5. Sheet E-1 has several notes which state " reconnect to
existing circuit", for the purpose of installation and inspection please identify these circuits.
6. Sheet E-2, connect front exit light to a circuit, general lighting circuit in general area- un-switched.
7. Sheet E-4, on the load calculation for panel R1, show the loads panel C has for this panel in the proper columns. This panel will be replaced with a new 42 circuit panel, the loads and curcuits are to be listed and described considering constant changes and need for exact information to be on panel.


Ray T Majuta
Electrical Plan Ck,
PDS City of Tucson
8/20/09
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2009 CPIERCE1 OUT TO CUSTOMER Completed
08/27/2009 SUE REEVES REJECT SHELF Completed