Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01922
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/20/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
07/20/2009 | RRICH1 | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the condensate drains per Section 307.2.2, IMC 2006, as amended by the City of Tucson. 2. Revise the control sequence of the restroom fans to prevent recirculation of the air from the restrooms. Reference: Section 403.2.1 (3), IMC 2006. 3. Indicate the air flow quantities for the restroom supplies. 4. Replot the drawings so that the backgrounds are visible. |
07/20/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
07/20/2009 | RRICH1 | WATER | REVIEW | Approved | |
07/20/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-3: RESTROOMS DO NOT MEET ACCESSIBILITY REQUIREMENTS. OPTION TO APPEAL BUILDING OFFICIAL, ERNIE DUARTE, TO REVIEW THIS PROJECT UNDER ADAAG. 2. GENERAL: PROVIDE BREAKDOWN OF PROJECT COSTS TO SHOW MAXIMUM OF 20% SPENT ON ACCESSIBILITY ISSUES. |
07/20/2009 | RRICH1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
07/20/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
07/20/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
07/24/2009 | CPIERCE1 | WWM | REVIEW | Needs Review | |
07/24/2009 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
07/24/2009 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
07/24/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |