Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01908
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/17/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
07/17/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Coordinate the operation of the new exhaust fan with the air conditioning. |
07/17/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/17/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/17/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/17/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
07/17/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the sizes of the new and existing waste piping. 2. Provide specifications for the new grease interceptor. 3.Show how the water temperature at the lavatory will be limited to 110 degrees Fahrenheit. |
07/17/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
07/17/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
07/17/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/17/2009 | RONALD BROWN | ADA | REVIEW | Passed | not a cot owned/operated project |
07/20/2009 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/20/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |