Review Details: REVISION - - 1ST
Permit Number - T09CM01905
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/24/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:4380 N Oracle Rd. T09CM01905--Revision Tenant Improvement The Electrical Plans for this project have been denied for the following: 1. The following Sheets Have a cloud and delta 3 indicating "Entire Sheet Revised" , E1.0, E2.0, E2.2,and E5.1. The following are entirely new Sheets which have been added, E3.0, E3.1, and E3.2. In order to properly review these plans , provide previous approved plans in order to determine scope of change. Ray T Majuta Electrical Plan Ck, DPDS< City of Tucson 11/25/09 Ray.Majuta@tucsonaz.gov |
| 11/25/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a duct smoke detector in the return air duct for RTU-4, upstream of any outside air connections. Reference: Section 606.1, IMC 2006. |