Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01905
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/21/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-7.4; SECTION 8: HEADER CALLS OUT REFERENCE TO SCHEDULE 16/A7.6. REVISE. 2. SHEET A7.4; SECTIONS 2 AND 6: TOP OF WALL MUST BE BRACED TO EXISTING STRUCTURE TO RESIST LATERAL LOAD PER 2006 IBC, SECTION 1607.13. 3. GENERAL: A MINIMUM OF 3/32" LETTERING IS REQUIRED ON ALL SHEETS. 4. GENERAL: INDICATE ON THE DRAWINGS THE PROJECT COST BREAKDOWN INCLUDING 20% MAXIMUM FOR ACCESSIBILITY ISSUES PER 2006 IBC, SECTION 3409.7. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL COMMENTS. |
| 07/22/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/22/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 07/29/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/29/2009 | RMYERS1 | WATER | REVIEW | Passed | |
| 07/30/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/13/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/09/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 09/09/2009 | SUE REEVES | REJECT SHELF | Completed |