Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM01901
Parcel: 11618348C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01901
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM01901
1313 W. ST Marys Rd

Project denied for thr following reasons:

1. Per City of Tucson commercial submittal requirements font size to be min 3/32" all upercase.

2. Per City of Tucson commercial submittal requirements need to include IECC light budget calculations and switching.

3. Lighting plan E1 shows duplex receptacle tied in with switch leg in RM 102 and switch leg controlled by flourescent dimmer.

4. Air conditioning loads to be calculated per NEC 220.50 and 440.6 exception #1. Branch cicuit selection current is given in table on sheet M1.

5. Per City of Tucson Commercial submittal requirements and NEC 220.50, 440.7 include 25% for largest motor load in load calculations.

Please respond to each item individually.

Rich Jiroudek 520-954-0161
Electric Pln Chk
9/3/09
09/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the notes on sheet M1 that call for the restroom exhaust fans to be interlocked to an unknown item.
2. Provide a smoke detector in the return air duct, upstream of any outside air connections, for HP-2. Reference: Section 606.1, IMC 2006.
09/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the proposed water heater platform is to be supported safely from the building structure. Reference: Section 314.5, UPC 2006.
2. Provide a drain to an approved location for the watertight pan under the water heater. Reference: Section 508.4, UPC 2006.
3. Provide a vacuum relief for the storage-type water heater. Reference: Section 608.7, UPC 2006.
4. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the instantaneous water heater that delivers a 41degree Fahrenheit rise to the lavatory faucet can guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. (Also, the Bosch Model RP3P appears to be an obsolete model.)
5. Provide a drinking fountain that meets the accessibility requirements as shown in Section 1109.5, IBC 2006. (A permanently connected water dispenser with cups mounted at an accessible height is an acceptable alternative.)

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
09/15/2009 SUE REEVES REJECT SHELF Completed