Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01901
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/03/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM01901 1313 W. ST Marys Rd Project denied for thr following reasons: 1. Per City of Tucson commercial submittal requirements font size to be min 3/32" all upercase. 2. Per City of Tucson commercial submittal requirements need to include IECC light budget calculations and switching. 3. Lighting plan E1 shows duplex receptacle tied in with switch leg in RM 102 and switch leg controlled by flourescent dimmer. 4. Air conditioning loads to be calculated per NEC 220.50 and 440.6 exception #1. Branch cicuit selection current is given in table on sheet M1. 5. Per City of Tucson Commercial submittal requirements and NEC 220.50, 440.7 include 25% for largest motor load in load calculations. Please respond to each item individually. Rich Jiroudek 520-954-0161 Electric Pln Chk 9/3/09 |
09/14/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the notes on sheet M1 that call for the restroom exhaust fans to be interlocked to an unknown item. 2. Provide a smoke detector in the return air duct, upstream of any outside air connections, for HP-2. Reference: Section 606.1, IMC 2006. |
09/14/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the proposed water heater platform is to be supported safely from the building structure. Reference: Section 314.5, UPC 2006. 2. Provide a drain to an approved location for the watertight pan under the water heater. Reference: Section 508.4, UPC 2006. 3. Provide a vacuum relief for the storage-type water heater. Reference: Section 608.7, UPC 2006. 4. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the instantaneous water heater that delivers a 41degree Fahrenheit rise to the lavatory faucet can guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. (Also, the Bosch Model RP3P appears to be an obsolete model.) 5. Provide a drinking fountain that meets the accessibility requirements as shown in Section 1109.5, IBC 2006. (A permanently connected water dispenser with cups mounted at an accessible height is an acceptable alternative.) |