Permit Number: T09CM01851
Parcel: 120063130

Address:
4201 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T09CM01851
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2009 RONALD BROWN ZONING HC REVIEW Approved
09/28/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The rim elevation of the next upstream manhole (MH# 5932-19) is not shown. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson
09/29/2009 ANDREW CONNOR LANDSCAPE REVIEW Denied 1) The screening requirement is in addition to the landscape requirements. The use of vegetation to satisfy the screen requirement is allowed, and is not meant to imply that the vegetative screen can be used to meet the landscape requirement DS 2-06.3.7. Vegetative coverage along 6th Ave does not meet 50% requirement. Revise plan as necessary.

2) Show by detail on the landscape plan how site will accommodate water harvesting. Place Detail B on the landscape plan to avoid confusion during construction.