Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01850
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/17/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/24/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/24/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information regarding the construction of the wall behind the recirculating Type I hoods to show that the hood installation complies with Section 507.9, IMC 2006 for clearances or provide the listing information for the hoods showing clearance requirements. Reference: Section 106.3.1, IMC 2006. |
| 07/31/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Passed | |
| 07/31/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/12/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/02/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/02/2009 | SUE REEVES | REJECT SHELF | Completed |