Permit Number: T09CM01847
Parcel: 12713036G

Address:
5910 E 5TH ST 01

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01847
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2009 GERRY KOZIOL WWM REVIEW Denied NEED PCRWRD 3RD FLOOR REVIEW-BUILDING IN PUBLIC SEWER EASEMENT-DON WILLHOIT 740-6779
10/22/2009 DAVE MANN FIRE REVIEW Approved
10/26/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 6: DID NOT LOCATE THE PETITION OF APPEAL FOR ACCESSIBILITY TO THE ALTAR/SOLEA AREA. PLEASE PROVIDE.
2. SHEET S1.1: PROVIDE CRITERIA FOR MASONRY (USED PER DETAIL 8/S5.3).
3. SHEET S3.1; STRUCTURAL CALCULATIONS SHEET A4: DID NOT LOCATE J1 ON CALCULATION SHEET A4 OR ON SHEET S3.1. PLEASE PROVIDE.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL COMMENTS IN THIS REVIEW.
10/27/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
11/03/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Item not addressed. The applicable code for all commercial projects is 2006 UPC with local ammendments. Provide an approved appeal to the building official if the plans are to be reviewed per the 2006 IPC.
11/03/2009 RMYERS1 WATER REVIEW Denied 1. Item not addressed. Provide the location and the size, of both the water service meter, and the reduced pressure backflow preventer assembly. Reference: 103.2.3 2006 UPC.
11/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Item not addressed. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Item not addressed. The HVAC equipment shall meet the mandatory provisions and prescriptive requirements of Sections 503.1 and 503.3, IECC 2006.
3. Comment not resolved. Detail 6/A4-1 appears to show the units base-mounted above a gyp-board ceiling, detail 7/M6.0 shows units suspended from the building structure over a lay-in ceiling, and a note on sheet M2.2 says that the units are to be relocated sometime in the future. Show how the fan coils are being installed. Reference: Sections 106.3.1 and 302.1, IMC 2006.
4. Item not resolved; the ducts appear to obstruct access to the new access panel and EHW-2 is still located in the same space. Show how adequate access is being provided for the fan coil units located above the ceiling (show also how EHW-2 will fit in the same space as AHU-2). Reference: Section 306.3, IMC 2006.
5. Item not addressed. Show the size, routing, and termination points of the primary and secondary condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
6. Item not addressed. Provide calculations demonstrating adequate ventilation. Reference: Section 403, IMC 2006.
7. Item not addressed. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006.
11/09/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 5910 E 5th St, T09CM01847
New Buildging, Church



The Electrical Plans for this project denied for the same reason as previously stated.
City of Tuscon Commercial Submittal Requirements dictate the need to show compliance with City of Tucson/Pima County Outdoor Ord #10135, this ordinance can be located on the City Web Page,under Departments, then Development Services then to Building Codes then Outdoor Ord.

Ray T Majuta
Elect Pln Ck
PDSD City of Tucson
11/09/09
Ray.Majuta@tucsonaz.gov
11/18/2009 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2009 SUE REEVES OUT TO CUSTOMER Completed
12/15/2009 SUE REEVES REJECT SHELF Completed