Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T09CM01847
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2009 | DAVE MANN | FIRE | REVIEW | Denied | Please include the following fire sprinkler design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. The Doors 104 D and E require panic hardware. |
| 07/17/2009 | SREEVES1 | ADA | REVIEW | Passed | |
| 07/21/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED PCRWRD 3RD FLOOR REVIEW-BUILDING IN PUBLIC SEWER EASEMENT-DON WILLHOIT 740-6779 |
| 07/24/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-0.1: DID NOT FIND A TOTAL OCCUPANCY LOAD FOR PROJECT. PROVIDE CALCULATION ON PLAN SHEET. 2. SHEET A-0.1: DID NOT FIND VERIFICATION FOR REQUIRED NUMBER OF PLUMBING FIXTURES PER IBC CHAPTER 29. PROVIDE CALCULATION ON PLAN SHEET, INCLUDING WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINKS. 3. SHEET A-2.1A: VERIFY WHEELCHAIR SPACES ARE PROVIDED PER IBC TABLE 1108.2.2.1. INDICATE THOSE SPACES ON PLAN. 4. SHEET A-2.1A: VERIFY WHEELCHAIR AISLE SEATS ARE PROVIDED PER IBC SECTION 1108.2.4. INDICATE THOSE SEATS ON PLAN. 5. SHEET A-2.1A: VERIFY ASSISTIVE LISTENING SYSTEM IS PROVIDED PER IBC SECTION 1108.2.6. INDICATE ON PLAN. 6. SHEET A-2.1A: THE ALTAR/SOLEA AREA MUST BE HANDICAP ACCESSIBLE PER IBC SECTION 1108.2.7, INCLUDING THE RESTROOM AT THE SACRISTY. VERIFY. 7. SHEET A-2.1A: PROVIDE INFORMATION ON THE SLIDING DOORS, LOCATED EITHER SIDE OF THE ALTAR, FOR COMPLIANCE WITH IBC SECTION 1008.1.3.3. 8. SHEET A-6.0; DOOR SCHEDULE: PROVIDE PANIC HARDWARE ON EXIT DOORS AS REQUIRED BY THE IBC SECTION 1008. 9. SHEET S3.1; ROOF JOISTS AT THE OFFICE, SACRISTY, AND BY THE STAIR: ARE THE JOIST SIZES CALLED OUT ON PLAN OR REFERENCED? PLEASE INDICATE SIZE AND SPACING, OR SPECIFIC REFERENCE. 10. SHEET S5.3: THERE ARE TWO 5/S5.3 DETAILS ON THIS SHEET. REVISE. 11. GENERAL: THERE WERE NO STRUCTURAL CALCULATIONS OR GEOTECHNICAL REPORT PROVIDED FOR THIS REVIEW. A COMPLETE STRUCTURAL REVIEW WILL BE NECESSARY FOR THE NEXT SUBMITTAL, AND MAY INCLUDE ISSUES NOT ADDRESSED IN THIS REVIEW. 12. GENERAL: ALL DEFERRED SUBMITTAL REQUESTS MUST BE APPROVED BY THE BUILDING OFFICIAL, ERNIE DUARTE. 13. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL COMMENTS IN THIS REVIEW. |
| 07/28/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 07/28/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 07/30/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. |
| 07/30/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. The HVAC equipment shall meet the mandatory provisions and prescriptive requirements of Sections 503.1 and 503.3, IMC 2006. 3. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 4. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006. 5. Show how adequate access is being provided for the equipment located on the roof. Reference: Section 306.5, IMC 2006. 6. Show how adequate access is being provided for the fan coil units located above the ceiling (show also how EHW-2 will fit in the same space as AHU-2). Reference: Section 306.3, IMC 2006. 7. Show the size, routing, and termination points of the primary and secondary condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 8. Provide calculations demonstrating adequate ventilation. Reference: Section 403, IMC 2006. 9. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. |
| 07/30/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the location and size of both the water service meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006. |
| 08/07/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 5910 E 5th ST T09CM01847 New Blgd, Church The Electrical Plans have been denied for the following; City of Tucson Commercial Submittal Requirements need to include and show full compliance with The City of Tucson/Pima County Outdoor Lighting Ord. #10135. You can locate this information on the City's web page, under Departments,Development Services, and to Building Codes. Ray T Majuta PDS City of Tucson Electrical Plan Chec k 8/10/09 Ray.Majuta@tucsonaz.gov |
| 08/13/2009 | TERRY STEVENS | ZONING | REVIEW | Denied | Per special exception condition #8, the maximum height of the dome is 43'-0" above finished grade. Building plans indicate the height of the dome as 43'-71/2" above finished floor which is 6" above finished grade for a total overall height of 44'-11/2". Revise plans or a change to the approved site plan will be required. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/21/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 09/21/2009 | SUE REEVES | REJECT SHELF | Completed |