Permit Number: T09CM01840
Parcel: 124040010

Address:
1448 E 1ST ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01840
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied KEYNOTES PP A1.O ARE CONFLICTING. KEYNOTE 3 INDICATES 6' HIGH FENCE, BUT SECTION SHOWS AN 8' HIGH WALL. KEYNOTE 4 INDICATES DOOR BUT IS ALSO ATTACHED TO WHAT APPEARS TO BE A FENCE. PLEASE COORDINATE ALL INFORMATION ON THIS PAGE.


PROVIDE CALCULATIONS FOR MASONRY FENCE AND FOUNDATIONS
04/14/2010 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
04/14/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
04/14/2010 LEERAY HANLY ZONING HC REVIEW Passed
04/14/2010 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Passed