Permit Number: T09CM01840
Parcel: 124040010

Address:
1448 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01840
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2009 DAVE MANN FIRE REVIEW Approved
07/17/2009 GERRY KOZIOL WWM REVIEW Passed
07/21/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-1.0; DETAIL 2: PROVIDE CALCULATIONS FOR MASONRY FENCE AND FOUNDATION (EXCEEDS 6' IN HEIGHT).
2. SHEET A-1.0; SPECIFICATION NOTES: ADD MATERIAL SPECIFICATIONS FOR MASONRY, GROUT, CONCRETE, REINFORCING, AND METAL STUDS.
3. GENERAL: PROVIDE COMPARISON OF WEIGHTS OF MECHANICAL EQUIPMENT TO BE ADDED AGAINST WEIGHTS OF MECHANICAL EQUIPMENT TO BE REMOVED. CALCULATIONS MUST BE PROVIDED TO ENSURE EXISTING STRUCTURE AT ALL FLOORS AND ROOF ARE CAPABLE OF SUPPORTING THOSE LOADS.
4. GENERAL: PROVIDE COST ANALYSIS FOR THIS PROJECT, INCLUDING THE 20% MAXIMUM SPENT ON ACCESSIBILITY ISSUES PER THE 2006 IBC, SECTION 3409.7.
07/21/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/21/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
07/27/2009 ROBERT SHERRY WATER REVIEW Approved
07/27/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the relationship of the existing 1-1/4" gas pipe located east of the existing gas meter and serving the kitchen appliances with the existing gas meter. Reference: Section 103.2.3, UPC 2006.
2. Does the 2" gas pipe shown connected to the existing gas meter have a pressure regulator? Reference: Section 103.2.3, UPC 2006.
3. How are gas pipes serving the existing water heaters and the furnace being replaced by F-1 related to the new and existing gas pipes? Reference: Section 103.2.3, UPC 2006.
4. What is the capacity of the existing gas meter? Reference: Section 103.2.3, UPC 2006.
07/27/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Replot sheets M-1, M-2, and M-3 to show the ductwork that is notated but not currently shown. Reference: Section 106.3.1, IMC 2006.
2. If the new condensate drains are to be connected to existing condensate drains (e.g. HP-9 and F-1), verify that the termination of the existing condensate drains complies with the current code requirements. Reference: Sections 102.4 and 307.2.1, IMC 2006, as amended by the City of Tucson.
08/10/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT:1448 E 1ST
T09CM01840
TI Sorority

Sheet E-6 list the service entrance conductors as 3 sets of 4# 500MCM's which amount to (380x3) =1140 amps.The 2005 NEC Section 240-4 C requires where if overcurrent device is rated over 800 amps, that the ampacity of the conductors it protects shall be equal to the overcurrent device or greater. Everything else ok.


Ray T Majuta
Elect Plan Ck
PDS City of Tucson
8-11/09
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2010 DELMA ROBEY OUT TO CUSTOMER Completed
03/08/2010 SUE REEVES REJECT SHELF Completed