Permit Number: T09CM01839
Parcel: 13507444E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01839
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
07/15/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the truss submittal that shows that the structure can accomodate the new rooftop A/C units.
07/15/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/15/2009 ROBERT SHERRY WATER REVIEW Approved
07/15/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/15/2009 JASON GREEN ENGINEERING REVIEW Approved
07/15/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plans and details to show how the water heater is to be supported.
2. Clarify the termination point for the T&P relief; there is no mop sink in this tenant space.
3. Show how the hot water temperature at the lavatories is to be limited to 110 degrees Fahrenheit.
07/15/2009 DAVE MANN FIRE REVIEW Approved
07/15/2009 RONALD BROWN ZONING HC SITE REVIEW Passed
07/15/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
07/21/2009 GERRY KOZIOL WWM REVIEW Approved
07/21/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review