Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE
Permit Number - T09CM01836
Review Name: RESUBMITTAL - SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The Appeal to the Building Official must be signed by the appellant and the owner. The appeal, along with a receipt for the appeal fee, is to be submitted separately from the drawings. 2. What is the source of the code amendment attached to the appeal; it is not an amendment contained in any codes adopted by the City of Tucson. 3. A manning roughness factor of 0.009 is not suitable for sewer design. A value of 0.013 provides allowance for interior coatings (e.g. grease), flow disturbances due to rough joints or pipe misalignment and for future pipe condition. In addition, the submitted calculation has a result that is not supported by the input data. 4. Any calculations submitted with the appeal shall be sealed by an Arizona registrant. |
| 10/07/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 10/09/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/21/2009 | RONALD BROWN | ADA | REVIEW | Denied | 1. All requests for ADAAG accessibility parking appeals must be made directly to the Office of Equal Opporunity Programs (OEOP) in care of Mr. Martin DuPont. 2. Please submit a letter of Deferred Submittal to Mr. LeeRay Hanly, Planning and Development Services Department, 201 N. Stone, for the Concessions booth. |